Problems can be avoided by the selection of the optimum and economic processes for the treatment of your own water. The
basis for the water quality to be achieved comprises the applicable
drinking water regulations or the specific customer requirements on the
water (e.g. service water). JUDO produces computer-assisted designs
and comprehensive quotations in combination with water analyses or
water samples and the local conditions on site, giving you the
guarantee of perfect drinking water or service water.
JUDO offers you more: Free water analyses + computer-assisted design + choice of the optimum processes + comprehensive quotations and advice + ongoing consultation on site + commissioning and maintenance by our nationwide customer service network = customer care that creates confidence
Data and analysis values for computer-assisted design
» Origin: spring water, mixed or surface water » Usage purpose of the treated water » Maximum water consumption per year, month, day » Peak throughflow (l/s, m³/h) » Number of residential units/people » Description of any difficulties occurring » Material type and nominal size of piping » Spring pump: piston pump or circulating/immersion pump » Maximum supply volume » Maximum lifting height/source depth » Compressed air chamber: capacity, switch-on pressure, switch-off pressure » Installation location: length, width, height » Smallest access on the way to the installation location: height, width » Drainage connection available? Nominal size? » Electricity connections in the installation room: 230 V / 50 Hz, 400 V / 50 Hz
Water constituents
Regulation limit TrinkwV (Germany)
Unit
1. pH-level
6,5 - 9,5
-
Need
2. Calcite solvent capacity
5
mg/l
Need
3. Temperature
-
°C
Need
4. Conductivity
2500
µS/cm
Need
5. Total slat content
-
mg/l
Desired
6. Iron (Fe++)
0,2*
mg/l
Need
7. Manganese (Mn++)
0,05*
mg/l
Need
8. Calcium (Ca++)
-
mg/l
Need (alternative 10)
9. Magnesium (Mg++)
-
mg/l
Need (alternative 10)
10.Total earth alkalis or total hardness
-
mmol/l °dH
Need (alternative 8+9)
11. Acid capacity KS 4,3 or carbonate hardness
-
mmol/l °dKH
Need
12. Sodium (Na+)
200
mg/l
Desired
13. Nitrate (NO3-)
50
mg/l
Need
14. Nitrite (NO2-)
0,5
mg/l
Need
15. Sulfate (SO4--)
250
mg/l
Need
16. Chlorine (Cl-)
250
mg/l
Need
17. Bacteriological assessment
* for systems below 1,000 m³/year: limit values - iron < 0.5 and manganese < 0.2 mg/l
Just give us a call, we are always here for you!
This page shows you pictures of your JUDO contacts.
Please give us a call or send us an e-mail – we will offer you an
optimum solution both from a technical and economic point of view...
Would you like a non-binding quotation on a solution for your specific problem?
Please use the following questionnaire, and fill it out completely. We
also require a current water analysis from you, or you can send us a
water sample taken on site.