Maximum expected water throughflow (according to DVGW Notice W 314)

Application area Maximum expected water throughflow in m³/h
4 5 6 8 9 10 11 12 13 14 15 20 25 30

Hospital
Beds

30 40 50 65 75 85 95 100 115 125 135 180 230 300

Office building
Employees

160 200 240 340 380 440 480 540 600 660 730 1100 1500 2000

Hotels
Beds

20 25 30 40 45 55 55 60 65 70 75 100 125 155

Department store
Employees

40 50 60 85 95 115 115 125 135 150 160 220 300 400